HBC Series

HBC/X

  • Commercial Chilled Water Ceiling Fan Coil
  • Horizontal 300–1200 CFM
  • PSC Motor or ECM Motor Options
  • Multiple Configuration Options: Ceiling Concealed, Plenum, Recessed, Exposed

Description

  • Commercial chilled water ceiling fan coil unit available in horizontal configuration with 300–1200 CFM capacity. Offers PSC or ECM motor options with flexible coil configurations (2-pipe, 4-pipe) and multiple installation styles.
Configurations
Air Conditioner
Voltage
115-120/1/60208-230/1/60265-277/1/60
Motors
PSCECM

Standard Features

  • Heavy gauge galvanized steel construction with zero clearance to combustible material approval
  • Plenums and cabinets insulated with Tuf-Skin dual density fiber glass blanket insulation with anti-microbial agent
  • Hinged access/return panels manufactured with heavy gauge galvanized steel with captive mounting screws and white baked powder finish
  • Positive sloped drain pans of galvanized steel with inside insulation coating and both primary and secondary drain connections
  • Coils constructed with seamless copper tubes and headers, mechanically expanded into corrugated aluminum fin material
  • Coils tested under water at 450 PSI for operation at 300 PSI with manual air vents
  • Double width, double inlet (DWDI) forward curved centrifugal fan wheels, statically and dynamically balanced
  • Standard PSC motors are permanently lubricated with internal thermal overload protection
  • ECM motor option includes 24V controls, constant torque permanent magnet brushless DC motor with 4 discrete speed taps for precise air balancing